02_NVspec_ver202e_pdf.xls

 1

_Object Model

1.Specification

1-1.Object Model

LMAP can be connected with the following models made by MITSUBISHI ELECTRIC CORPORATION.

<Model name>

1

.

Multiple split type air conditioners CITY MULTI

2.

Split-type air conditioners Mr.SLIM

NOTE:Mr.SLIM is necessary for A-M Converter(PAC-SF48MA-E)

3.

Heat recovery ventilators LOSSNAY

NOTE:LOSSNAY is necessary for LOSSNAY Adapter(PZ-53ADF-E/PZ-52SF-E)

1-2.Explanation of Function Setting

The function set switch is necessary for this product because of connected model and the control function from L

ON

W

ORKS

.

SW NO.

SW NO.

SW NO.

SW NO.

switch name

switch name

switch name

switch name

Function

Function

Function

Function

Note

Note

Note

Note

Factory

Factory

Factory

Factory

setting

setting

setting

setting

Set timing

Set timing

Set timing

Set timing

SW1-1

SW1-1

SW1-1

SW1-1

Function switch of local prohibit 

ON

ON

ON

ON local prohibit effective

Operation local prohibit nv input from
L

ON

W

ORKS

 becomes Effective when switch ON.

OFF

Before turning on

the power supply

OFF local prohibit invalidity

Operation local prohibit nv input from
L

ON

W

ORKS

 becomes invalid when switch OFF.

SW1-2

SW1-2

SW1-2

SW1-2

Used together with MELANS switch

ON

ON

ON

ON

used together
with MELNAS

OFF

Before turning on

the power supply

OFF

not used together
with MELNAS

SW1-3

SW1-3

SW1-3

SW1-3

Indoor temperature state
interval switch

ON

ON

ON

ON

Transmission interval
 (

1

minutes or more)

*The number of indoor unit should be
 connected 30 or less

OFF

Before turning on

the power supply

OFF

Transmission interval
 (

1

0 minutes or more)

SW1-5

SW1-5

SW1-5

SW1-5

Function switch of LOSSNAY

ON

ON

ON

ON

LOSSNAY is operation
from LONWORKS.

Please turn on the switch when LOSSNAY
is operation from L

ON

W

ORKS

.

OFF

Before turning on

the power supply

OFF

LOSSNAY interlocks
with the indoor unit

Please turn off the switch when LOSSNAY
interlocks with the indoor units.

SW1-6

SW1-6

SW1-6

SW1-6

Function switch of Mr.SLIM

ON

ON

ON

ON

Mr.SLIM is operation
from LONWORKS.

Please turn on the switch when Mr.SLIM
is operation from L

ON

W

ORKS

OFF

Before turning on

the power supply

*Function effective at SW

1

-2 OFF

OFF

Mr.SLIM is not operation
from LONWORKS.

SW1-9

SW1-9

SW1-9

SW1-9

Indoor units test run switch

ON

ON

ON

ON

ON(test run) is transmitted
to the indoor units

OFF

Always

OFF

OFF is transmitted
to the indoor units

SW3-2

SW3-2

SW3-2

SW3-2

Initialization switch of
the air conditioners units

ON

ON

ON

ON

Connected cancellation
command is transmitted to
 the indoor units

OFF

Always

OFF None

WLN0

1

-

1

023(Ver2.02)

- 2 -

Оглавление инструкции

  • Страница 1 из 26

    02_NVspec_ver202e_pdf.xls cover Version2.02 2001.02.06 AIR CONDITIONER INTERFACE MODEL: LMAP02-E PAC-YV02LMAP Network Variables Specification 1 2 3 4 5 6 Specification Object Details SNVT Table Network Variables Configuration Properties Node Object AppendixA: Communication timing when power supply

  • Страница 2 из 26

    02_NVspec_ver202e_pdf.xls 1_Object Model 1.Specification 1-1.Object Model LMAP can be connected with the following models made by MITSUBISHI ELECTRIC CORPORATION. <Model name> 1. Multiple split type air conditioners CITY MULTI 2. Split-type air conditioners Mr.SLIM NOTE:Mr.SLIM is necessary for A-M

  • Страница 3 из 26

    02_NVspec_ver202e_pdf.xls 2_Object Details 2 .Object Details 2-1.Overview Node Object Object Type #0 Network Variables Indoor[0] Network Variables Configuration Properties Indoor[1] Network Variables ・ ・ ・ ・ ・ Indoor[50] Network Variables Indoor[0]: The indoor all unit common item

  • Страница 4 из 26

    02_NVspec_ver202e_pdf.xls 2_Object Details 2-2.indoor unit Indoor[1]-[50] Network Variables nv1n nviOnOff_n SNVT switch nv2n nvoOnOff_n SNVT switch nv3n nviMode_n SNVT hvac mode nv4n nvoMode_n SNVT hvac mode nv5n nviSetPoint_n SNVT temp p nv6n nvoSetPoint_n SNVT temp p nv7n nviFanSpeed_n SNVT

  • Страница 5 из 26

    02_NVspec_ver202e_pdf.xls 2_Object Details 2-3.Mr.SLIM Indoor[1]-[50] Network Variables nv1n nviOnOff_n SNVT switch nv2n nvoOnOff_n SNVT switch nv3n nviMode_n SNVT hvac mode nv4n nvoMode_n SNVT hvac mode nv5n nviSetPoint_n SNVT temp p nv6n nvoSetPoint_n SNVT temp p nv7n nviFanSpeed_n SNVT switch

  • Страница 6 из 26

    02_NVspec_ver202e_pdf.xls 2_Object Details 2-4.LOSSNAY (1)LOSSNAY interlocks with the indoor unit.(note 1,3) Indoor[1]-[50] Network Variables nv14n nvoLCMode_n SNVT switch nv16n nvoAlarm_n SNVT switch (note.4) (2)LOSSNAY is operation from LONW ORKS.(note 5,6) Indoor[1]-[50] Network Variables nv1n

  • Страница 7 из 26

    02_NVspec_ver202e_pdf.xls 2_Object Details 2-5.Common ( note 1 ) Indoor[0] Network Variables nv11 nviAllOff_n SNVT switch Configuration Properties nciSndHrtBt_1 Send Heartbeat_1 nciSndHrtBt_2 Send Heartbeat_2 nciMinOutTm Minimum Send Time nciInitStartTm Initialize Start Time nciInitOutTm_1

  • Страница 8 из 26

    3.SNVT Table 02_NVspec_ver202e_pdf.xls 3_SNVT Table Model nv No. Name (note 1) (note 1) CITY LOSSNAY Mr.SLIM interlocks with the indoor unit MULTI SNVT Type input operation from LONWORKS output Transmitted when changing Auto update Initialize (note 2) Request On/Off 1n nviOnOff_n X X X SNVT_switch

  • Страница 9 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 4. Network Variables 1n Request On/Off network input SNVT_switch nviOnOff_n; This input network variable is used for ON or OFF request of the indoor unit or ventilator (in case of independent operation) . When the ventilator(LOSSNAY) is registered

  • Страница 10 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 3n Request mode network input SNVT_hvac_mode nviMode_n; This input network variable is used to change the operation mode of the indoor unit. This nv is not required to use when setting the operation mode only from the local side such as the local remote

  • Страница 11 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 13n Request LOSSNAY Mode network input SNVT_switch nviLCMode_n; This input network variable is used to change the operation mode of the ventilator (at independent operation without interlocking) . This nv is not required to use when setting the

  • Страница 12 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 5n Setpoint from network (Both cool and heat) network input SNVT_temp_p nviSetPoint_n; This input network variable is used to change the temperature setpoint of the indoor unit. * The set temperature applied is used for cool/dry/heat/auto modes and not

  • Страница 13 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 7n Request Fan Speed network input SNVT_switch nviFanSpeed_n; This input network variable is used to change the fan speed of the indoor unit or Ventilator (in case of independent operation). This nv is not required to use when setting the airflow rate

  • Страница 14 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 10n Thermo On/Off state network output SNVT_state nvoThermo_n; This output network variable indicates the On/Off state of the indoor unit, the thermostat (compressor command signal) and the auxiliary heater for heating. This nv is used to calculate the

  • Страница 15 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 16n Alarm state network output SNVT_switch nvoAlarm_n; This output network variable indicates the abnormality of the indoor unit. If the outdoor unit is in alarm state, the indoor unit also stops urgently. Therefore all indoor units in a same

  • Страница 16 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 19n Request Local Prohibit On/Off network input SNVT_switch nviProOnOff_n; This input network variable is used to prohibit the On/Off operation of the local remote controller connected to the indoor unit or ventilator (under independent operation

  • Страница 17 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 21n Request Local Prohibit mode network input SNVT_switch nviProMode_n; This input network variable is used to prohibit the mode change operation of the local remote controller connected to the indoor unit. Valid Range value field : not used state field

  • Страница 18 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 23n Request Local Prohibit SetPoint network input SNVT_switch nviProSetP_n; This input network variable is used to prohibit the temperature setpoint change of the local remote controller connected to the indoor unit. Valid Range value field : not used

  • Страница 19 из 26

    02_NVspec_ver202e_pdf.xls 4_Network Variables 11 Request All Off network input SNVT_switch nviAllOff; This input network variable is used for the emergency Off of the indoor unit and all ventilation. Valid Range value field : not used state field : 0 = Emergency Off of indoor unit and ventilator :

  • Страница 20 из 26

    02_NVspec_ver202e_pdf.xls 5_Configuration 5.Configuration Properties (1) Send Heartbeat_1 network input config SNVT_time_sec nciSndHrtBt_1; This network configuration defines the time between the previous and next updating. When the set time is elapsed from the automatic update or change output of

  • Страница 21 из 26

    02_NVspec_ver202e_pdf.xls 5_Configuration (3) Minimum Send Time network input config SNVT_time_sec nciMinOutTm; This configuration property defines the minimum send time between the output network variables. The objective network variables are given below. ・nvoOnOff_n(On/Off Run State )

  • Страница 22 из 26

    02_NVspec_ver202e_pdf.xls 5_Configuration (5) Initialize Send Time_1 network input config SNVT_time_sec nciInitOutTm_1 This configuration property defines the minimum send time between the output network variables at initial output. This configuration is valid when setting the Initialize Start Time

  • Страница 23 из 26

    02_NVspec_ver202e_pdf.xls 5_Configuration (7) Send Heartbeat Start Time network input config SNVT_time_sec nciStartHrtBt This configuration property defines the start time of automatic updating at the powering of the LM-AP. The objective network configurations are given below. ・nciSndHrtBt_1(Send

  • Страница 24 из 26

    02_NVspec_ver202e_pdf.xls 6_node_object 6. Node Object 1n Object Request network input SNVT_obj_requst nviRequest; Valid Range object_id :0 =valid request :Else =invalid request object_request :2(RQ_UPDATE_STATUS) :Else =valid request =invalid request Default Value The default value is 0. 2n Object

  • Страница 25 из 26

    02_NVspec_ver202e_pdf.xls AppendixA Communication timing when power supply of LM-AP is turned on Power Supply Initialized Processing t Usually Processing 0 (7)nciStartHrtBt (1)nciSndHrtBt_1 (8)nciStartOutTm (6)nciInitOutTm_2 (6)nciInitOutTm_2 Initialization of LM-AP (15 minutes or more)